CRAL150 | CRAL300 | CRAL300R | CRAL400 | CRAL400R | CRAL600 | CRAL800 | Custom | Components
Cool Laser Optics | Warranty

CRAL400 Series Self-Contained Free-Standing Chiller

 
CRAL400 - 400 Watt Free-Standing Chiller with side outlet by CustomChill, Inc. CustomChill Recirculating Liquid Chillers offer state-of-the-art, cost-effective solutions to meet your critical cooling and /or heating applications. The CRAL400 series chillers are rated 400 Watts cooling capacity and are offered in 115V or 230V, 50/60Hz input power. The CRAL400 free standing chiller offers a multitude of features.

Standard features include:

  • Programmable digital PID system controller
  • Low fluid level indicator or dry contact closure
  • Leak-proof fluid inlet and outlet quick disconnect valves
  • Highly reliable, environmentally safe thermoelectric cooling elements
  • Efficient seal-less magnetic drive pump with brushless DC motor
  • Quiet high performance fans
  • Offered as 115V or 230V, 50/60 Hz input power

Optional features include:

  • RS232/RS485 communication port
  • Higher flow and pressure capabilities
  • Heating option, up to 500 Watts
  • Flow control (alarm)
  • Temperature alarm


CRAL400 - 400 Watt Free-Standing Chiller with front hose by CustomChill, Inc. Product Specifications     PDF Version     User Manual

Model Number

CRAL400-115

CRAL400-230

Input Voltage, VAC 115 230
Frequency, Hz 50/60 50/60
Current Draw, Amps 7.2 3.5
Cooling Capacity, (Watts/Btuh) 400 / 1364 400 / 1364
Max. Ambient Temperature, °C/ °F 50 / 122 50 / 122
Min. Ambient Temperature*, °C/ °F -10 / 14 -10 / 14
Max Flow Rate, lpm/gpm 6 / 1.6 6 / 1.6
Max Pressure @ 0 Flow, PSI 14.7 14.7
Chiller Fluid Capacity, ml/Gal 750 / 0.20 750 / 0.20
Noise Level, dBA 50 50
Heating Capacity**, Watts 500 500
Control Temperature Range***, °C/ °F -12 to 41 /
10.4 to 106
-12 to 41 /
10.4 to 106
Temperature Control Accuracy, °C/ °F ± 0.10/ ± 0.18 ± 0.10/ ± 0.18
Dimensions    
Height, in/mm 13.5 / 330 13.5 / 330
Width, in/mm 7.75 / 197 7.75 / 197
Depth, in/mm 11 / 279 11 / 279

Notes:
* Minimum ambient temperature is given for equipment performance only, it doesn’t take into consideration type of fluid used. To avoid fluid freezing, always use proper antifreeze.
** Optional 500W heating feature available.
*** For fluid temperatures above 41°C, please consult factory.

Performance